Mode of Operation:This
counter is programmed using the panel push switches to set the batch size and a
4 way switch at the rear to set the modes.
Single shot Mode - Up count:
Pulses are counted from zero until the batch size is reached then the relay is
energised.
The count will continue if more pulses are applied to the input but the relay remains
energised until the counter is reset.
Single shot Mode - Down count:
The count is preset to the batch size and counts down to zero then the relay is
energised.
The count will remain at zero and the relay remains
energised until the counter is reset.
Cycle Mode - Up
count: Pulses
are counted from zero until the batch size is reached then the relay is
energised and the
counter is reset and continues to count. The relay remains energised for a
period that can be set between 0.1 and 5 seconds.
Cycle Mode - Down
count: The
count is preset to the batch size and counts down to zero then the relay is
energised and the
counter is reset to the preset value and continues to count. The relay remains energised for a
period that can be set between 0.1 and 5 seconds.
Specification
Modes:
cycle/single-shot
Count direction:
up
or down
Setting:
Push-Push switches
Inputs:
Reset, Pulse, Up-down select
Input type:
Selectable
for PNP or NPN type sensors or volt free contact
Relay output:
Single pole changeover contacts - 5 amp at 240VAC or 30VDC
Supply:
115/240 VAC or 12 - 30 VDC
Power output:
12 volt DC output @ 50mA for powering
sensors etc.