Mode of Operation:This
counter is programmed using the panel push switches to set the batch size and a
4 way switch at the rear to set the modes.
Single shot Mode - Up count:
Pulses are counted from zero until the batch size is reached then the relay is
energised.
The count will continue if more pulses are applied to the input but the relay remains
energised until the counter is reset.
Single shot Mode - Down count:
The count is preset to the batch size and counts down to zero then the relay is
energised.
The count will remain at zero and the relay remains
energised until the counter is reset.
Cycle Mode - Up
count: Pulses
are counted from zero until the batch size is reached then the relay is
energised and the
counter is reset and continues to count. The relay remains energised for a
period that can be set between 0.1 and 5 seconds.
Cycle Mode - Down
count: The
count is preset to the batch size and counts down to zero then the relay is
energised and the
counter is reset to the preset value and continues to count. The relay remains energised for a
period that can be set between 0.1 and 5 seconds.